PUMP TESTING PROCEDURE

 

GAUGE TEST

 

Each water pressure gauge must be checked for accuracy at a minimum of 3 points, including 150 psi (10 bar), 200 psi (14 bar), and 250 psi (17 bar). Any gauge that is off by more than 10 psi (0.7 bar) must be recalibrated, repaired, or replaced.